Description
Features:
- Meanwell SMPS Power Supply
- Universal AC input / Full range
- Built-in active PFC function
- Protections: Short circuit / Overload / Over voltage / Over temperature
- 5″×3″ compact size
- Free air convection for 160w and 360w with 20.5 CFM forced air
- Medical safety approved (2 × MOOP between primary to secondary) (Note.10)
- With power good and fail signal output
- Built-in remote sence funciton for 5~15v
- No load power consumption under 0.75W by PS-ON control (G model)
- Standby 5V 0.8A with fan, 0.6A without fan (G model)
- Fixed switching frequency at 65KHz
- 3 years warranty
Detailes:
MODEL |
ANP-160-15 |
ANP-160-24 |
ANP-160-48 |
|
OUTPUT |
DC VOLTAGE |
15V |
24V |
48V |
RATED CURRENT (20.5CFM) |
10.3A |
6.5A |
3.25A |
|
CURRENT RANGE (convection) |
0 ~ 7.3A |
0 ~ 4.6A |
0 ~ 2.3A |
|
CURRENT RANGE (20.5CFM) |
0 ~10.3A |
0 ~6.5A |
0 ~3.25A |
|
RATED POWER (convection) |
112.5W |
113.4W |
113.4 |
|
RATED POWER (20.5CFM) |
159.5W |
161W |
161W |
|
RIPPLE & NOISE (max.) |
120mVp-p |
150mVp-p |
250mVp-p |
|
VOLTAGE ADJ. RANGE |
CH1:13.5 ~ 16.5V |
CH1:22 ~ 27V |
CH1:43.2 ~ 52.8V |
|
VOLTAGE TOLERANCE |
±3.0 % |
±2.0 % |
±2.0 % |
|
LINE REGULATION |
±0.5 % |
±0.5 % |
±0.5 % |
|
LOAD REGULATION |
±1.0 % |
±1.0 % |
±1.0 % |
|
SETUP, RISE TIME |
1800ms, 30ms/230VAC 3500ms , 30ms/115VAC at full load |
|||
HOLD UP TIME (Typ.) |
16ms/230VAC/115VAC at full load |
|||
INPUT |
VOLTAGE RANGE |
90 ~ 264VAC 127 ~ 370VDC |
||
FREQUENCY RANGE |
47 ~ 63Hz |
|||
POWER FACTOR (Typ.) |
PF larger than 0.93/230VAC, PF larger than 0.98/115VAC at full load |
|||
EFFICIENCY (Typ.) |
85% |
85% |
85% |
|
AC CURRENT (Typ.) |
2A/115VAC 1.1A/230VAC |
|||
INRUSH CURRENT(Typ.) |
COLD START 35A/115VAC 70A/230VAC |
|||
LEAKAGE CURRENT |
Earth leakage current less than 200µA / 264VAC, Touch current less than 100µA/264VAC |
|||
PROTECTION |
OVERLOAD |
105 ~ 135% rated output power |
||
Protection type : Hiccup mode, recovers automatically after fault condition is removed |
||||
OVER VOLTAGE |
5.75 ~ 6.75V |
5.75 ~ 6.75V |
5.75 ~ 6.75V |
|
Protection type : Shut down o/p voltage, re-power on to recover |
||||
OVER TEMPERATURE |
110°C(5V), 105°C(12V, 15V, 24V, 48V)(TSW1: detect on heatsink of power transistor) |
|||
95°C(5V), 90°C (12V, 15V, 24V, 48V) (TSW2: detect on heatsink of power transistor) |
||||
Protection type : (TSW1) Shut down o/p voltage, recovers automatically after temperature goes down |
||||
Protection type : (TSW2) Shut down o/p voltage, re-power on to recover |
||||
FUNCTION |
5V STANDBY |
5VSB: 5V at 0.6A without fan, 0.8A with fan 20.5CFM; tolerance ±2%, ripple: 50mVp-p (max.) |
||
PS-ON INPUT SIGNAL (G model) |
Power on: PS-ON=“Hi” or “larger than 2~5V”; |
|||
Power off: PS-ON= “Low” or “0~0.5V” |
||||
POWER GOOD / POWER FAIL |
500ms larger than PG larger than 10ms; PF larger than 1ms |
|||
REMOTE SENSE |
17.25 ~ 20.25V |
27.6 ~ 32.4V |
55.2 ~ 64.8V |
|
ENVIRONMENT |
WORKING TEMP. |
-20~ +70°C (Refer to derating curve) |
||
WORKING HUMIDITY |
20 ~ 90% RH non-condensing |
|||
STORAGE TEMP., HUMIDITY |
-40 ~ +85°C , 10 ~ 95% RH |
|||
TEMP. COEFFICIENT |
±0.03%/°C (0 ~ 50°C) |
|||
VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes |
|||
SAFETY & EMC |
SAFETY STANDARDS |
ANSI/AAMI ES60601-1, TUV EN60601-1, IEC60601-1 approved |
||
WITHSTAND VOLTAGE |
I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC |
|||
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25°C/ 70% RH |
|||
EMC EMISSION |
Compliance to EN55011 (CISPR11), EN55022 (CISPR22) , Class B, EN61000-3-2,-3 |
|||
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN60601-1-2, criteria A |
|||
OTHERS |
MTBF |
230.5K hrs min. MIL-HDBK-217F (25°C ) |
||
DIMENSION |
127*76.2*34.6mm (L*W*H) |
|||
PACKING |
0.32Kg; 36pcs/12.5Kg/0.79CUFT |
|||
NOTE |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance: includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directive. 5. HS1,HS2 & HS3 can not be shorted. 6. Derating may be needed under low input voltages. Please check the derating curve for more details. 7. The rated power includes 5Vsb at 0.6A 8. The rated power includes 5Vsb at 0.8A 9. Touch current was measured from primary input to DC output. 10. Suitable for BF application with appropriate system consideration |